Adjusting the EECO UV-5A

There are a few small variations on the EECO UV-5A (UV-5AT, UV-5ATC, etc.). These instructions will work for any version.

Your valve is basically pre-adjusted. please do not go to factory pre-sets!

Follow these steps to get started:

1. Watch Getting Started Video

2. Bypass Adjustment

  • Start pump, making sure that NO solenoid coils are energized
  • Turn the BPS adjustment in (clockwise) until the car just begins to move
  • Next, turn the BPS adjustment out (counter-clockwise) until the car stops, then out a half turn more, and stop the pump

3. Operating Adjustments

  • Make normal runs up and down, making minor adjustments as necessary to attain the desired operation

4. Pressure Relief Setting

  • Install pressure gauge
  • Determine operating pressure with fully loaded car
  • Close pit valve
  • Back out pressure relief adjustment
  • Register an up call and adjust pressure according to local code, but not more than 25% higher than loaded operating pressure

5. Call For Assistance

We are happy to help you get the valve adjusted. Please call us at 208-754-4884 if you have any issues.

Learn More

For valve features, and videos, visit the full UV-5A page.